Zoned exponential, vertical and horizontal ultra-clean laminar airflows: No differences in bacteriological efficiency
DOI:
https://doi.org/10.3109/17453679809117621Abstract
We compared the novel zoned exponential ultra-clean operating room ventilation, needing no extra side-walls with the traditionally used ultra-clean air systems having vertical or horizontal laminar airflow, but requiring extra side-walls. The three units were evaluated with regard to elimination of particles with focus on airborne and sedimenting bacteria-carrying particles (colony forming units, cfu) during rigidly standardized sham operations. Although minor differences were recorded inside the ultra-clean air-flows, the three systems were comparable with regard to bacteriological efficiency and ensured a low air and surface contamination (0.05-4 cfu/m3 and 7-72 cfu/m2/h, depending on the site of sampling). We conclude that all three systems fulfilled well the criteria for ultra-clean air (< 10 cfu/m3), but that exponential airflow is the most versatile alternative, as additional side-walls around the operating area can be omitted.Downloads
Download data is not yet available.
Downloads
Published
1998-01-01
How to Cite
Friberg, B. E. E., Burman, L. G., & Friberg, S. (1998). Zoned exponential, vertical and horizontal ultra-clean laminar airflows: No differences in bacteriological efficiency. Acta Orthopaedica, 69(2), 169–172. https://doi.org/10.3109/17453679809117621
Issue
Section
Articles
License
Acta Orthopaedica (Scandinavica) content is available freely online as from volume 1, 1930. The journal owner owns the copyright for all material published until volume 80, 2009. As of June 2009, the journal has however been published fully Open Access, meaning the authors retain copyright to their work. As of June 2009, articles have been published under CC-BY-NC or CC-BY licenses, unless otherwise specified.